Electrical Enclosure Cooling — Fans for Cabinets That Run Cool
Cabinet fans, control cabinet ventilation, panel cooling: same physics every time — every watt of load you shed inside the enclosure raises temperature until air exchange carries it out. This page is how we size AC axial fans for electrical cabinets, PLC cabinets, VFD cabinets, box transformers and storage containers.
The three numbers that size a cabinet fan
1 — Heat to remove
Sum the losses of everything inside (drives, supplies, contactors all state their heat rejection). That is your W to shed.
2 — Allowed temperature rise
Components are usually specified to 40–55 °C internal. Subtract worst-case ambient — that gap buys the airflow.
3 — Real path resistance
Filters, louvres and grilles eat static pressure. An axial fan in free air loses flow quickly once a filter bank is added — that is why we publish PQ curves per model.
The practical rule we work to: place intake low and exhaust high, one fan can pressurise and the other exhausts, and design so the worst corner stays inside the component limit. For filter-and-fan panels, derate published free-air airflow using the model's pressure curve, not the headline CFM.
What we supply for cabinet duty
- 120×120×38 mm guarded fans — the workhorse size for control cabinets and PLC panels.
- 80–92 mm compact fans for terminal boxes and small panel sections.
- 172–220 mm frames for VFD cabinets, welding machines and cabinet rows.
- 230 V as standard; 115 V for North American panels; 380 V three-phase for industrial cabinets.


Cabinet exhaust fan layout notes
One intake low, one exhaust high, opposing diagonal corners of the cabinet. Keep the intake away from adjacent cabinet walls. Where dust or washdown matters, fit filter fans or sealed grilles and re-check the duty against the PQ curve before ordering — or send us the drawing and we will do that check for you, free.
IP-rated enclosures need a different calculation (no air path) — tell us the IP class you must keep.
Industries running our enclosure fans
Telecom network cabinets, power cabinets, box-type transformers, dry-type transformers, ev charging piles and energy-storage containers, data centers, medical devices, power supplies and power electronics, cold rooms and cold-chain equipment, welding machines and air-purification systems.
Send the cabinet drawing and heat load.
We return the model, quantity and mounting layout.